Ravel 12 Zone Conventional Fire Alarm Panel


HSN Code - 853180
Product Code - AISS

Brief Description -

The microprocessor based CE mark 12 Zone conventional fire alarm control panel, the system has 20 X 4 LCDcharacter with alpha numeric touch key pad, 12 zones detection circuit, 3 common programmable potential free contacts & 2 common NAC sounder output, inbuilt Rs-485 for Networking – TCP/IP, peer to peer & repeater connectivity, central monitoring facility, inbuilt RTC with Event logs, wall/ceiling mounted, Switch mode power supply- SMPS & Battery polarity & Deep discharge protection.


  • Complies with UL -864 and NFPA-72.
  • 20 x 4 Dot Matrix LCD Display.
  • Operates on 120 – 220v 60 /50 Hz, AC Mains power supply.
  • Standby (battery) backup 24v DC power supply with builtin charger.
  • Touch Keypad for user friendly operation.
  • Epoxy powder coated finish.
  • Class- B, Style B / C initiating device circuit (IDC).
  • All zones accept smoke detectors and any normally open contact device.
  • Class B Notification Appliance Circuits (NAC).
  • NAC shall be programmed as auto silence / Silence Inhibit.
  • Error free Fire / Fault status in unambiguous colored LED indication.
  • 1000 Event storage with RTC.
  • Main, Standby status with audible and visual indication.
  • Two Form C relays for fire and fault.
  • Resettable / Steady 24V D.C. Output.
  • RS 485 Communication facility.
  • TCP/IP facility (Optional)
  • MODBUS for BMS integration (Optional).
  • PC software (optional)
  • External Zone Wise Sounder/Contact via RS 485 (Optional).
  • All field wiring circuits are supervised.
  • Zone Isolation facility with loop voltage cut off.
  • Zones available : 12, 16, 20, 24, 32, 48, 64,96 and 128.
  • Facility to connect Public Address System (PA) through RS-485 Communication.
  • Peer to Peer network facility.
  • Maximum 16 panels can be connect in a Single Network.

 

Electrical Specification

Primary Power
120 – 220VAC ± 10%, 60 / 50 Hz.
Initiating Device Circuits
All zones are
Class B Style B/C operation (Programmable).
Normal Operating Voltage   :   14 – 21 VDC.
Alarm Current   :   15 – 30mA.
Short Circuit Current   :   45mA Maximum.
Loop resistance   :   100 ohms Maximum.
End-Of-Line Resistor   :   4K7, 1/2watt
Standby Current   :   7mA (2.5mA for Detectors)
Standby Power
24V D.C
Quiescent current   :   120 mA
 
Operating Condition
Operating Temperature   :   0 – 49° C/32-120° F.
Relative Humidity   :   93 ± 2% RH (non- condensing) at 32 ±2° C/90 ±3° F.
 

Charging Circuit
Charging Voltage   :   28.0V, ±0.5V
Charging Current   :   1.2A(Max);

 

D.C. Output(Resettable / Steady)
24VDC Output ,1A Max.

 
Common Relays
Type   :   Form C
No of Relays   :   2
Relay Contact Rating   :   2Amps @ 30 VDC, 0.5Amps @ 125VAC.
Power Factor   :   1.0
Notification Appliance Circuits
Class B Style – Y wiring
Operating Nominal Voltage   :    24VDC
Special Application Current   :   from 12 Zone Upto 64Zone
NACs   :   2 Amps (1 A per circuit) Current above 64Zone
NACs   :   4 Amps (1 A per circuit)
Line Drop   :   1.8V
End-Of-Line Resistor   :   4K7, 1/2watt

 

Dimensions

Zones Width Height Depth
12 Zone 425 350 120
16 Zone 425 350 120
20 Zone 500 600 160
24 Zone 500 600 160
32 Zone 500 600 160
48 Zone 600 700 160
64 Zone 600 1000 160
96 Zone 600 1400 160
128 Zone 600 1400 160

 

Ordering Information

Models Description
RE-9012 12 Zone Fire Alarm Control Panel
RE-9016 16 Zone Fire Alarm Control Panel
RE-9020 20 Zone Fire Alarm Control Panel
RE-9024 24 Zone Fire Alarm Control Panel
RE-9032 32 Zone Fire Alarm Control Panel
RE-9048 48 Zone Fire Alarm Control Panel
RE-9064 64 Zone Fire Alarm Control Panel
RE-9096 96 Zone Fire Alarm Control Panel
RE-9128 128 Zone Fire Alarm Control Panel

Compatible Devices

Model Description
RE-900RP Series Fire Alarm Repeater Panel