Product Name -
Ravel 16 Zone Conventional Fire Alarm Panel


HSN Code - 853180
Product Code - AISS

Brief Description -

The microprocessor based CE mark 16 Zone conventional fire alarm control panel, the system has 20 X 4 LCD character with alpha numeric touch key pad, 12 zones detection circuit, 3 common programmable potential free contacts & 2 common NAC sounder output, inbuilt Rs-485 for Networking – TCP/IP, peer to peer & repeater connectivity, central monitoring facility, inbuilt RTC with Event logs, wall/ceiling mounted, Switch mode power supply- SMPS & Battery polarity & Deep discharge protection.


  • Complies with UL -864 and NFPA-72.
  • 20 x 4 Dot Matrix LCD Display.
  • Operates on 120 – 220v 60 /50 Hz, AC Mains power supply.
  • Standby (battery) backup 24v DC power supply with builtin charger.
  • Touch Keypad for user friendly operation.
  • Epoxy powder coated finish.
  • Class- B, Style B / C initiating device circuit (IDC).
  • All zones accept smoke detectors and any normally open contact device.
  • Class B Notification Appliance Circuits (NAC).
  • NAC shall be programmed as auto silence / Silence Inhibit.
  • Error free Fire / Fault status in unambiguous colored LED indication.
  • 1000 Event storage with RTC.
  • Main, Standby status with audible and visual indication.
  • Two Form C relays for fire and fault.
  • Resettable / Steady 24V D.C. Output.
  • RS 485 Communication facility.
  • TCP/IP facility (Optional)
  • MODBUS for BMS integration (Optional).
  • PC software (optional)
  • External Zone Wise Sounder/Contact via RS 485 (Optional).
  • All field wiring circuits are supervised.
  • Zone Isolation facility with loop voltage cut off.
  • Zones available : 12, 16, 20, 24, 32, 48, 64,96 and 128.
  • Facility to connect Public Address System (PA) through RS-485 Communication.
  • Peer to Peer network facility.
  • Maximum 16 panels can be connect in a Single Network.

 

Specification

 

  • Electrical Specification
  • Primary Power
  • 120 – 220VAC ± 10%, 60 / 50 Hz. Initiating Device Circuits
  • All zones are
  • Class B Style B/C operation (Programmable).
  • Normal Operating Voltage : 14 – 21 VDC.
  • Alarm Current : 15 – 30mA.
  • Short Circuit Current : 45mA Maximum.
  • Loop resistance : 100 ohms Maximum.
  • End-Of-Line Resistor : 4K7, 1/2watt
  • Standby Current : 7mA (2.5mA for Detectors)
  • Standby Power
  • 24V D.C
  • Quiescent current : 120 mA
  • Operating Condition
  • Operating Temperature : 0 – 49° C/32-120° F.
  • Relative Humidity : 93 ± 2% RH (non- condensing) at 32 ±2° C/90 ±3° F.
  • Charging Circuit
  • Charging Voltage : 28.0V, ±0.5V
  • Charging Current : 1.2A(Max);
  • D.C. Output(Resettable / Steady)
  • 24VDC Output ,1A Max.
  • Common Relays
  • Type : Form C
  • No of Relays : 2
  • Relay Contact Rating : 2Amps @ 30 VDC, 0.5Amps @ 125VAC.
  • Power Factor : 1.0 Notification Appliance Circuits
  • Class B Style – Y wiring
  • Operating Nominal Voltage : 24VDC
  • Special Application Current : from 12 Zone Upto 64Zone
  • NACs : 2 Amps (1 A per circuit) Current above 64Zone
  • NACs : 4 Amps (1 A per circuit)
  • Line Drop : 1.8V
  • End-Of-Line Resistor : 4K7, 1/2watt
  • Dimensions
  • Zones Width Height Depth
  • 12 Zone 425 350 120
  • 16 Zone 425 350 120
  • 20 Zone 500 600 160
  • 24 Zone 500 600 160
  • 32 Zone 500 600 160
  • 48 Zone 600 700 160
  • 64 Zone 600 1000 160
  • 96 Zone 600 1400 160
  • 128 Zone600 1400 160