Call NowCall Now
Call now Call Now

All India Safety Services

Product Name -
Ravel 2 Zone Conventional Fire Alarm Panel


HSN Code - 853180
Product Code - AISS

Brief Description -

The RE-102R is a 2 Zone Fire Alarm Control Panel,which uses conventional input devices. The Outputs include Notification Appliance Circuits (sounders), two programmable Form – C relays, RS-485
port to interface with annunciators and optional zone wise sounder & zonewise contact. The FACP is field programmable via the panel keypad. It alsosupervises all wiring, AC voltage and battery level. Optional ethernet, & GSM ports are user for transmission.


CE Approved.

16 X 2 Dot Matrix LCD Display.

Standby battery backup with built in charging.

Switch Mode Power Supply.

Tactile Keypad for easy panel operation.

System ON indication.

Low Battery visual warning with audible tone.

Fire / Fault status in unambiguous colored LED indication.

2 programmable relays for fire, supervisory and fault.

All zones accept smoke detectors and any normally open contact device.

Any Zone can be configured as alarm or supervisory.

Zone wise isolation and one man walk test facility.

Programmable Aux Outputs.

Lamp test & Drill test facility.

100 All Events log with RTC.

Date / Time / Password configuration.

Programmable auto silence facility.

Zone wise sounder / contact (optional).

TCP-IP / GSM facility (optional).

All field wiring circuits are supervised.

 

Specification

 

Primary Power
120 / 230VAC + 10% -15%, 60 / 50 Hz, 50W
Standby Power
24VDC (2 Nos of 12V, 3.5Ah Sealed Lead acid battery)
Operating Condition
Operating Temperature 0 – 49° C / 32 – 120° F.
Storage Temperature 0 – 60° C
Relative Humidity 93 ± 2% RH (non-condensing) at 32 ± 2° C / 90 ± 3° F
Quiescent Current
2 Zone
4 zone
40mA
50mA
Charging Circuit
Charging voltage
Charging current
28 V ± 5%
350mA (max)
24VDC
Quantity
Voltage
Current
1 No
24VDC continuous or resettable (Regulated)
100mA (max)
Notification Appliance Circuits
Wiring style
Quantity
Operating voltage
Current
EOL resistor
Class B
1 No
24VDC (Regulated)
350mA
4K7, ½ watt
Relays
Type
Quantity
Relay contact rating
Power factor
Form C
2 No’s (Programmable)
1A @ 30 VDC
1.0
Initiating Device Circuits
Wiring style
Quantity
Normal operating voltage
Alarm current
Short circuit current
Loop resistance
EOL Resistor
Standby Current
Class B
2 or 4 (102R- 104R)
14 – 21 VDC
15 – 35 mA
42 mA (max)
50 Ω (max)
4K7, ½ watt
6.8 mA (2.4 mA for detectors)
RS 485
Nodes
Wiring Style
Wire type
Circuit Length
Loop resistance
1
Class B
Twisted pair
1.2 Km (Max)
100 Ohms


call
Whatsapp
email