Morley Mi Dczrm Addressable Zone Monitor Module


HSN Code - 853110
Product Code - AISS

Brief Description -

The MI-DCZRM addressable zone monitor module allows a zone of non-addressable devices to communicate with a Morley-EN protocol analogue addressable system. The module monitors a zone of two-wire non-addressable devices. Each MI-DCZRM uses one of 99 available module addresses on a loop. A fault signal will be transmitted to the panel in case of an open circuit or short circuit on the non-addressable zone wiring or when the external fault input is pulled low (can be used for power supply monitoring).


  • • Connection of a zone of non-addressable detectors to an analogue addressable fire system
  • • Built in isolation allowing system installation in stages without loss of protection
  • • Monitors open circuit and short circuit • TRI-Colour Status LED
  • • Zone powered from addressable loop wiring or external 24V PSU
  • • Remote reset of non-addressable zone
  • • Compatible with: Most non-addressable detectors IS non-addressable detectors
  • • Monitoring of external power supply • External fault input
  • • CPD approval to EN54-17 and EN54-18, LPCB and VdS
  • • DIN rail mountable, consistent with all other modules
  • • Support for an extended power supply range as low as 18Vdc 60mA with an External PSU